    Title: 綠建築與空調系統之個案研究
    A Case Study of Air Conditioning System for Department Stores by the Green Building Assessment Mechanism
    Authors: 林立人
    Dumas
    Contributors: 冷凍空調系
    Keywords: 綠建築;空調節能;日常節能指標
    Green building;Energy conservation for air-conditioning;Energy saving indicator
    Date: 2008
    Issue Date: 2008-10-06 14:07:23 (UTC+8)
    Abstract: 台灣是個資源欠缺的島國,高達98%能源需仰賴進口,而空調之使用已是現代人生活中不可或缺的必需品,但其耗電量卻高達夏季總電量的35%,為了人類之永續發展,節約能源已是世界各國共有的目標,而其具體的作法,現今最為普遍的就是使用綠建築評估指標,因此本論文研究之目的,旨在探討綠建築與空調節能之關係。
    本論文之研究先以文獻追溯法,分析現今國內外對綠建築議題所進行之評估方法,作為研究基礎;次者以我國目前施行之綠建築評估指標為範本,取一百貨商場空調系統作為案例,研究空調系統之規劃、設計與分級等三階段評估,最後搭配不同的空調技術作為改善對策,讓人易於接受空調節能之評估精神,並樂於在建築設計中納入;最後以歸納法,對空調節能做出結論及建議。
    本研究所探討之空調節能改善方法計有:主機效率提昇、外氣處理與使用太陽能等,共五種方法,其最經濟的技術為使用外氣冷房系統;而再生能源系統的使用,對資源欠缺的台灣而言,未來最具發展潛力。
    本論文研究結果顯示:1.本案例之空調節能評估指標EAC每改善1%,每年可節省111,631度之用電,約占本案例全年耗電1%;2.施用不同之節能空調技術,將造成系統改變,需注意衍生之相關問題;3.空調節能評估指標EAC愈低,空調節能分級評估指標之得分將愈高,表示節能效率愈好;4.對空調系統耗能比例高之部份進行改善,所得效果較高;5.空調節能與建築外殼是息息相關的,外殼耗能指標ENVLOAD & 外周區係數γ愈大,則空調愈耗能。
    Appears in Collections:[Department of Refrigeration & Air Conditioning] 【冷凍空調與能源系】博碩士論文