Experimental Investigation of a Machine Tool Cooler Using Hot-gas By-pass Valves for Temperature Control
作者:
王輔仁
貢獻者:
冷凍空調與能源系
日期:
2011-02
上傳時間:
2017-11-29 09:52:43 (UTC+8)
摘要:
Machine tool with more accurate, stable and higher precision for the machining components cannot be developed without the precise control of the temperature rise by appropriate cooling. The machine tool coolers are the best managers of oil (or water) temperature in avoiding the deviation of spindle centerline for machine tools. However, the machine tool coolers are facing the control hunting of cooling temperature and the dramatic variation of heat load during high speed machining. In this study, the experimental investigation using hot-gas by-pass scheme were conducted to evaluate the temperature control accuracy of process cooling water. Effects of delay time control use pulse width modulation (PWM) techniques for by-pass valve under variation of process cooling load and different throttling devices been have investigated. The accuracy of temperature control as well as the frequency of ON-OFF times under different loading and different delay time has been compared comprehensively. The experimental results revealed that control accuracy within 0.2 °C (0.36 °F) of cooling water temperature can be achieved with 5 seconds delay time controlled by adjusting hot-gas by-pass valve. The proposed hot-gas by-pass cooling system with PWM controlled time delay scheme is not only more cost-effective than inverter-driven system, but also can provide higher durability for by-pass solenoid valve and perform precise temperature control specific for high-accuracy process cooling application. © 2011 ASHRAE. (15 refs)
關聯:
ASHRAE Transactions
顯示於類別:
[冷凍空調與能源系(所)] 【冷凍空調與能源系】期刊論文
文件中的檔案:
沒有與此文件相關的檔案.
檢視Licence
在NCUTIR中所有的資料項目都受到原著作權保護.
DSpace Software
Copyright © 2002-2004
MIT
&
Hewlett-Packard
/
Enhanced by
NTU Library IR team
Copyright ©
-
回饋